Manufacturer |
N/A State® |
Input Power |
N/A 500000 BTU/hr |
Tank Size |
N/A 85 U.S. gal322 L |
First Hour Rating |
N/A 545 U.S. gal2062 L |
Standard Shipping Weight |
N/A 812 lb368 kg |
ASME Shipping Weight |
N/A 857 lb388 kg |
Thermal Efficiency |
N/A 80 % |
Maximum Hydrostatic Working Pressure |
N/A 160 psi |
Style |
N/A Sandblaster® |
Size |
N/A C |
Type |
N/A Gas |
Industry Standards |
N/A ANSI Z-21.10.3 - CSA 4.3 ASHRAE/IESNA 90.1 ASME Certified CSA® 4.3 NSF UL® Listed |
Recovery at 40 ºF Temperature Rise |
N/A 1212 gal/h |
Recovery at 22 ºC Temperature Rise |
N/A 4588 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 479 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 1813.2 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 346 gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 1311 L/h |
Top Inlet/Outlet Water Connection |
N/A 1-1/2 in |
Front Inlet/Outlet Water Connection |
N/A 1-1/2 in |
Back Inlet/Outlet Water Connection |
N/A 1-1/2 in |
AC Voltage |
N/A 120 V |
Current |
N/A 0.7 A |
AC Voltage with Power Venter |
N/A 120 V |
Full Load Current |
N/A 3 A |
Features |
N/A
Self-Cleaning Hydro Cannon™
|
Testing and Certifications |
N/A
|
Other Features |
N/A
Fully Automatic Control System
|
Options |
N/A
Manifold Kits for Multiple Heater Installations
|
Note |
N/A
Maximum gas supply pressure (natural and propane gas): 13.8" w.c. Minimum gas supply pressure, natural gas: 4.5" w.c. Minimum gas supply pressure, propane gas: 10" w.c. Manifold pressure, natural gas: 3.5" w.c. Manifold pressure, propane gas: 10" w.c. Induced Draft design, Category I Venting |