Specifications

Manufacturer

N/A State®

Nominal Storage Capacity

N/A 500 U.S. gal

Input Power

N/A 2500000 BTU/hr

First Hour Rating

N/A 2824 gal

Shipping Weight with Burner

N/A 4419 lb

Motor Power

N/A 3/4 hp

Type

N/A Natural Gas

Style

N/A State Titan® Large Volume

Size

N/A C

Industry Standards

N/A ASHRAE/IESNA 90.1 ASME Certified CSA® Certified UL® Listed

Maximum Recovery

Recovery at 80 ºF Temperature Rise

N/A 3030 gal/h

Recovery at 100 ºF Temperature Rise

N/A 2424 gal/h

Recovery at 140 ºF Temperature Rise

N/A 1732 gal/h

Dimensions

Schematic

N/A
Schematic Drawing for State Titan® LV Large Volume Power Burner - Gas, Oil and Dual-FuelCommercial Water Heaters (TPG)

Dimension A

N/A 108 in

Dimension B

N/A 15 in

Dimension C

N/A 2 in

Dimension D

N/A 32-1/2 in

Dimension E

N/A 2 in

Dimension F

N/A 55 in

Dimension G

N/A 16 in

Dimension H

N/A 91-1/2 in

Dimension J

N/A 100 in

Electrical Characteristics

Current

N/A 10.2 A

Voltage

N/A 120 V

Frequency

N/A 60 Hz

Features

Features

N/A
  • Meets the thermal efficiency and standby loss requirements of U.S. Department of Energy and current edition of ASHRAE/IESNA 90.1.
  • UL - Entire unit UL listed (File No. MH11631).
  • Low Nox - Complies with Texas low NOx and Air Quality Management Districts with requirements of less than 30 ppm.
  • Glasslined Tank - Exclusive corrosion protection with glasslining on all interior surfaces. Multiple anodes provide even more corrosion protection.
  • ASME Construction Standard - 160 PSI working pressure on all models.
  • Power Gas Burner - Power burner has electronic flame safeguard control with intermittent spark ignition. Also included are main and pilot automatic gas valves plus gas pressure regulators, diaphragm air switch for proof of blower operation.
  • Fully Automatic Controls With Safety Shutoff - High temperature limit control (manual reset). CSA® Certified and ASME rated T&P Relief Valve. Hinged door control compartment for ease of access. Two thermostats, upper and lower, for accurate temperature control. Standard control is for 120 ºF - 180 ºF water service.
  • Jacket And Insulation - Heavy gauge steel with baked powder coat finish. Insulated with high-density foam insulation that meets or exceeds all required standards.
  • Factory Start-up Included - Required for activating warranty and assuring maximum operating performance.

Other Features

Other Features

N/A
  • Two layers of high temperature ceramic fiber insulation in combustion chamber
  • Flame inspection port opening
  • Mounted on rugged channel iron skids
  • Combination temperature and pressure gauge
  • Low water cutoff
  • ASME rated temperature and pressure relief valve
  • Barometric draft regulator
  • Two cleanout inspection openings
  • 120 volt control circuit
  • Drain valve
  • Removable lifting lugs

Note

Note

N/A Certified Minimum Installation Clearances to Combustibles:
  • Front: 18 inches
  • Back: 0 inches
  • Sides: 0 inches
  • Top: 5 inches
A clearance of 24 inches should be maintained from serviceable parts such as relief valve, power burner, drain valve and anodes (Anodes are located on side above cold water inlet).

Minimum gas supply pressure: 7 Inches W.C.
Maximum gas supply pressure: 13 Inches W.C.

TPG models are Category I appliances (Fan Assisted) and require a negative draft. These units should only be commonly vented with other Category I negative draft appliances per the latest addition of the National Fuel Gas Code. An approved/listed Type "B" venting material is recommended. A negative draft of -0.02" to -0.07 is required in the vent.