Print Back
Designed for use as a recovery heater having its own storage tank.
Unit of Measure

Specifications

Manufacturer

State®

Tank Capacity

80 gal300 L

Standard Input Power

6 kW

Input Power

20478 BTU/hr

Inlet/Outlet (NPT)

1-1/4 in3.2 cm

Approximate Shipping Weight

280 lb127 kg

Number of Elements

3

Element Power

2000 W

Voltage

208 V240 V277 V480 V

Phase

Single Three

Working Pressure

150 psi1034 kPa

Style

Sandblaster® Surface Mount

Size

C

Type

Electric

Industry Standards

ASHRAE/IESNA 90.1 ASME Certified CSA® Certified cUL® Listed UL® Listed

Maximum Recovery

Recovery at 30 ºF Temperature Rise

82 gal/h

Recovery at 17 ºC Temperature Rise

310 L/h

Recovery at 40 ºF Temperature Rise

62 gal/h

Recovery at 22 ºC Temperature Rise

233 L/h

Recovery at 50 ºF Temperature Rise

49 gal/h

Recovery at 28 ºC Temperature Rise

166 L/h

Recovery at 60 ºF Temperature Rise

41 gal/h

Recovery at 33 ºC Temperature Rise

155 L/h

Recovery at 70 ºF Temperature Rise

35 gal/h

Recovery at 39 ºC Temperature Rise

133 L/h

Recovery at 80 ºF Temperature Rise

31 gal/h

Recovery at 45 ºC Temperature Rise

116 L/h

Recovery at 90 ºF Temperature Rise

27 gal/h

Recovery at 50 ºC Temperature Rise

103 L/h

Recovery at 100 ºF Temperature Rise

25 gal/h

Recovery at 56 ºC Temperature Rise

93 L/h

Recovery at 110 ºF Temperature Rise

22 gal/h

Recovery at 61 ºC Temperature Rise

85 L/h

Recovery at 120 ºF Temperature Rise

21 gal/h

Recovery at 67 ºC Temperature Rise

78 L/h

Recovery at 130 ºF Temperature Rise

19 gal/h

Recovery at 72 ºC Temperature Rise

72 L/h

Recovery at 140 ºF Temperature Rise

18 gal/h

Recovery at 78 ºC Temperature Rise

66 L/h

Dimensions

Schematic


Schematic Drawing for Sandblaster® Surface Mount Thermostats Commercial Electric Water Heaters

Dimension A

60-1/4 in153 cm

Dimension B

25-1/2 in64.8 cm

Dimension C

31 in78.7 cm

Electrical Characteristics

Full Load Current Single Phase 208 V

28.8 A

Full Load Current Single Phase 240 V

25 A

Full Load Current Single Phase 277 V

21.7 A

Full Load Current Single Phase 480 V

12.5 A

Full Load Current Three Phase 208 V

16.7 A

Full Load Current Three Phase 240 V

14.4 A

Full Load Current Three Phase 480 V

7.2 A

Features

Features

Meets the current edition of ASHRAE/IESNA 90.1 standards.

Gold Elements - CSB models ship with the gold plated elements. Patented gold elements provide long life and superior scaling resistance. Low watt density means lower surface temperature to minimize scale buildup and more surface to heat water. Gold elements carry a one-year warranty against failure due to lime scale build-up.

Glasslined Tank - Three sizes: 50, 80, and 119 gallon capacity. Tank interior is coated with glass specially developed for water heater use. Tanks rated at 150 psi (1034 kPa) working pressure (ASME 150 psi). Foam insulation reduces costly heat loss, and is vermin proof.

Fusing - Protects all elements, thermostats, and internal wiring circuits against excess current flow. Meets National Electrical Code requirements that non-ASME tanks must have internal fusing when current draw exceeds 48 amps.

Standard Voltages - 208, 240, and 480 V single-phase and three-phase delta. Convertible from three-phase to single -phase (in field) and vice versa. 277 V single-phase also available.

Terminal Block - Factory-installed. Just bring the service to the heater and connect to block.

Controls - One temperature control (adjustable through a range of 120 to 180 ºF) and manual reset high temperature cut-off per element. Thermostat step control may be achieved by varying settings on individual temperature controls. Located behind hinged control compartment door for quick, easy access.

Other Standard Features

Other Standard Features

  • Surface mounted thermostats
  • Simplified circuitry, color coded for ease of service
  • Two anode rods for maximum corrosion protection
  • Cabinet has bonderized undercoat with baked enamel finish
  • Bottom inlet and top outlet openings
  • Brass drain valve
  • CSA® certified and ASME Rated T&P Relief Valve
  • Single panel control box

Options

Options

  • UL and cUL listed conversion kits to adjust voltage and kW requirements in the field before and after installation
  • ASME 150 psi tank construction
  • International voltages - 220, 380, 400, 415, 575, and 600 volts, three phase available with Y connected elements
  • Manifold Kits - for multiple tank installations. Two heaters-part #9003429205, three heaters-part #9003430205 and four heaters-part #9003431205

Warranty

Warranty

  • 3-Year Limited Tank Warranty.

Note

Note

Not recommended for sanitizing water application.

Figured at 1 kW (3413 BTU) = 4.1 Gallons at 100 ºF temperature rise.