Print Back
The PowerFlex® commercial gas water heater has a factory mounted and wired blower that allows exhaust venting of up to 40' with 3" schedule 40 PVC pipe and 3 long sweep 90º elbows.
Unit of Measure

Specifications

Manufacturer

N/A American® Water Heater Company

Capacity

N/A 75 gal

Input Power

N/A 75100 BTU/hr

Recovery

N/A 69 gal/h

Size of Gas Connection

N/A 1/2 in

T and P Opening

N/A 3/4 in

Approximate Shipping Weight

N/A 265 lb

Elbow Angle

N/A 90 º

Pipe Material

N/A PVC

Style

N/A Powerflex® Power Vent

Size

N/A C

Type

N/A Natural Gas

Industry Standards

N/A ANSI Z-21.10.3 - CSA 4.3 C.E.C. Listed CSA® 4.3

Dimensions

Schematic

N/A
Schematic Drawing for PowerFlex® Commercial Gas Water Heaters

Jacket Diameter A

N/A 26 in

Height to Top of Vent B

N/A 70-1/4 in

Height to Top of Heater C

N/A 60 in

Vent Size

N/A 3 in

Top Connection Spread

N/A 11 in

Height Space Heat Out

N/A 53 in

Height Space Heat In

N/A 12-1/2 in

Height Gas Connection

N/A 12-1/2 in

Height to Side T and P D

N/A 53 in

Maximum Recovery

Recovery at 40 ºF Temperature Rise

N/A 173 gal/h

Recovery at 50 ºF Temperature Rise

N/A 138 gal/h

Recovery at 60 ºF Temperature Rise

N/A 115 gal/h

Recovery at 70 ºF Temperature Rise

N/A 99 gal/h

Recovery at 80 ºF Temperature Rise

N/A 86 gal/h

Recovery at 90 ºF Temperature Rise

N/A 77 gal/h

Recovery at 100 ºF Temperature Rise

N/A 69 gal/h

Recovery at 110 ºF Temperature Rise

N/A 63 gal/h

Recovery at 120 ºF Temperature Rise

N/A 58 gal/h

Recovery at 130 ºF Temperature Rise

N/A 53 gal/h

Recovery at 140 ºF Temperature Rise

N/A 49 gal/h

Features

Features

N/A
  • 2" Non-CFC Foam Insulation
    Foam insulation traps heat within the tank, saving energy.
  • Fused Ceramic Shield
    Applied under pressure and fired at 1600 ºF to completely cover the tank interior. This provides a tough interior surface for storage tanks and maximum protection against the wearing effects of high-volume and high temperature water.
  • Self-Cleaning Diff user Dip Tube
    Reduces scale and corrosive deposits that are detrimental to the life cycle of commercial water heaters.
  • Anode Rod
    Promotes longer tank life through protection against corrosion of tank interior.
  • Factory-Installed Temperature & Pressure Relief Valve.
  • Power Cord
    Supplied and wired for easy installation and service.
  • Propane Models
    Heavy duty cast iron burners.
  • Low NOx Burner
    On natural gas models.
  • Design Certified
    By CSA® International for up to 180 ºF as an automatic storage heater in compliance with the latest edition of ANSI Z21.10.3 and CSA®4.3 Standards.
  • California (CEC) and New York compliant.
  • Side Water Connections for Space Heating Applications.

Warranty

Warranty

N/A
  • 3-Year Limited Tank Warranty / 1-Year Parts Warranty.

Note

Note

N/A Limited warranty on tank and parts. Complete details in manual. Factory-installed side T&P opening version only. Side connections for space heating. Hot and cold water connections 1". Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.