Manufacturer |
N/A American® Water Heater Company |
Standard Type |
N/A Non-ASME |
Input Power |
N/A 199900 BTU/hr58 kW |
Thermal Efficiency |
N/A 95 % |
Approximate Capacity |
N/A 100 U.S. gal379 L |
Maximum Hydrostatic Working Pressure |
N/A 160 psi |
Standard Approximate Shipping Weight |
N/A 555 lb |
ASME Approximate Shipping Weight |
N/A 595 lb |
Minimum Supply Natural Gas Line Size (N.P.T.) |
N/A 3/4 in |
Minimum Supply Propane Gas Line Size (N.P.T.) |
N/A 3/4 in |
Type |
N/A Natural Gas |
Style |
N/A HCG Series |
Size |
N/A C |
Industry Standards |
N/A ANSI Z-21.10.3 - CSA 4.3 ASHRAE/IESNA 90.1 ASME Optional CSA® Certified Energy Star UL® Listed |
Recovery at 30 ºF Temperature Rise |
N/A 767 gal/h |
Recovery at 17 ºC Temperature Rise |
N/A 2904 L/h |
Recovery at 40 ºF Temperature Rise |
N/A 575 gal/h |
Recovery at 22 ºC Temperature Rise |
N/A 2178 L/h |
Recovery at 50 ºF Temperature Rise |
N/A 460 gal/h |
Recovery at 28 ºC Temperature Rise |
N/A 1743 L/h |
Recovery at 60 ºF Temperature Rise |
N/A 384 gal/h |
Recovery at 33 ºC Temperature Rise |
N/A 1452 L/h |
Recovery at 70 ºF Temperature Rise |
N/A 329 gal/h |
Recovery at 39 ºC Temperature Rise |
N/A 1245 L/h |
Recovery at 80 ºF Temperature Rise |
N/A 288 gal/h |
Recovery at 44 ºC Temperature Rise |
N/A 1089 L/h |
Recovery at 90 ºF Temperature Rise |
N/A 256 gal/h |
Recovery at 50 ºC Temperature Rise |
N/A 968 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 230 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 871 L/h |
Recovery at 110 ºF Temperature Rise |
N/A 209 gal/h |
Recovery at 61 ºC Temperature Rise |
N/A 792 L/h |
Recovery at 120 ºF Temperature Rise |
N/A 192 gal/h |
Recovery at 67 ºC Temperature Rise |
N/A 726 L/h |
Recovery at 130 ºF Temperature Rise |
N/A 177 gal/h |
Recovery at 72 ºC Temperature Rise |
N/A 670 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 164 gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 622 L/h |
AC Voltage |
N/A 120 V |
Frequency |
N/A 60 Hz |
Blower Current |
N/A 2.2 A |
Igniter Current |
N/A 4 A |
One 90º Elbows for Maximum 3" Vent Pipe |
N/A 45 ft13.7 m |
Two 90º Elbows for Maximum 3" Vent Pipe |
N/A 40 ft12.2 m |
Three 90º Elbows for Maximum 3" Vent Pipe |
N/A 35 ft10.7 m |
Four 90º Elbows for Maximum 3" Vent Pipe |
N/A 30 ft9.1 m |
One 90º Elbows for Maximum 4" Vent Pipe |
N/A 115 ft35 m |
Two 90º Elbows for Maximum 4" Vent Pipe |
N/A 110 ft33.5 m |
Three 90º Elbows for Maximum 4" Vent Pipe |
N/A 105 ft32 m |
Four 90º Elbows for Maximum 4" Vent Pipe |
N/A 100 ft30.5 m |
Five 90º Elbows for Maximum 4" Vent Pipe |
N/A 95 ft29 m |
Six 90º Elbows for Maximum 4" Vent Pipe |
N/A 90 ft27.4 m |
Features |
N/A
Fully Submerged, Spiral-Shaped Condensing Heat Exchanger
ASME Construction
|
Other Features |
N/A
Commercial Grade Glasslined Tank & Heat Exchanger
|
General Information |
N/A
Installation Considerations
|
Note |
N/A
Recovery capacities are based on heater performance at 95% and 96% thermal efficiency. For complete information on limited warranties, consult written warranty. Maximum gas supply pressure for 10.5" W.C. natural gas 14" propane gas. Manifold pressure: 4" W.C. natural gas 10" W.C. propane. Maximum number of 90º elbows allowed for the vent (exhaust) pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Maximum number of 90º elbows allowed for intake air pipe is four (4) when installing 3 inch pipe and six (6) when installing 4 inch pipe. Two (2) 45º elbows equal one (1) 90º elbow. Electrical requirements: 120 VAC/60 HZ, Blower 2.2 Amps FL, Igniter 4.0 Amps. Center line of water outlet on top of water heaters is approximately 7 inches from the front edge of the water heater |