Manufacturer |
N/A A. O. Smith® |
Input Power |
N/A 15 kW51195 BTU/hr |
Number of Elements |
N/A 3 |
Element Power |
N/A 5000 W |
Tank Capacity |
N/A 50 gal189 L |
Equipment Grade |
N/A Commercial |
Inlet/Outlet (NPT) |
N/A 1-1/4 in3.2 cm |
Approximate Shipping Weight |
N/A 265 lb120 kg |
Industry Standards |
N/A ASHRAE/IESNA 90.1 ASME Certified |
Full Load Current Single Phase 208 V |
N/A 72.1 A |
Full Load Current Single Phase 240 V |
N/A 62.5 A |
Full Load Current Single Phase 277 V |
N/A 54.2 A |
Full Load Current Single Phase 480 V |
N/A 31.3 A |
Full Load Current Three Phase 208 V |
N/A 41.6 A |
Full Load Current Three Phase 240 V |
N/A 36.1 A |
Full Load Current Three Phase 480 V |
N/A 18.0 A |
Standard Voltage |
N/A 208 V240 V480 V |
Recovery at 30 ºF Temperature Rise |
N/A 205 gal/h |
Recovery at 40 ºF Temperature Rise |
N/A 154 gal/h |
Recovery at 50 ºF Temperature Rise |
N/A 123 gal/h |
Recovery at 60 ºF Temperature Rise |
N/A 102 gal/h |
Recovery at 70 ºF Temperature Rise |
N/A 88 gal/h |
Recovery at 80 ºF Temperature Rise |
N/A 77 gal/h |
Recovery at 90 ºF Temperature Rise |
N/A 68 gal/h |
Recovery at 100 ºF Temperature Rise |
N/A 61 gal/h |
Recovery at 110 ºF Temperature Rise |
N/A 56 gal/h |
Recovery at 120 ºF Temperature Rise |
N/A 51 gal/h |
Recovery at 130 ºF Temperature Rise |
N/A 47 gal/h |
Recovery at 140 ºF Temperature Rise |
N/A 44 gal/h |
Recovery at 17 ºC Temperature Rise |
N/A 775 L/h |
Recovery at 22 ºC Temperature Rise |
N/A 582 L/h |
Recovery at 28 ºC Temperature Rise |
N/A 465 L/h |
Recovery at 33 ºC Temperature Rise |
N/A 388 L/h |
Recovery at 39 ºC Temperature Rise |
N/A 332 L/h |
Recovery at 45 ºC Temperature Rise |
N/A 291 L/h |
Recovery at 50 ºC Temperature Rise |
N/A 258 L/h |
Recovery at 56 ºC Temperature Rise |
N/A 233 L/h |
Recovery at 61 ºC Temperature Rise |
N/A 211 L/h |
Recovery at 67 ºC Temperature Rise |
N/A 194 L/h |
Recovery at 72 ºC Temperature Rise |
N/A 149 L/h |
Recovery at 78 ºC Temperature Rise |
N/A 166 L/h |
Features |
N/A
Economy Mode Operation - Control system automatically lowers the Operating Set Point by a programmed value during user-defined time periods. Helps reduce operating costs during unoccupied or off-peak demand periods. Linear Sequencing - Banks of heating elements (3 elements per bank) are energized according to adjustable (1 to 20º) differential set points for each bank. First bank on is the last bank off. Helps reduce current surge and provides accurate water temperature control. Goldenrod Elements - All DVE models ship standard with patented Goldenrod 24K gold plated elements. Goldenrod elements provide long life with superior scaling resistance. Glass-Lined Tank - Three sizes; 50, 80, and 119 gallon capacity. Tank interior is coated with glass specially developed by A. O. Smith® for water heater use. Tanks rated at 150 psi working pressure; tested at 300 psi. Foam insulation reduces costly heat loss. ASME (optional) maximum working pressure is 150 psi. Power Circuit Fusing - Protects elements and contactors from short circuits, overloading or line surges. Meets National Electric Code requirements (fusing required when current draw exceeds 48 amps). Standard Voltages - 208, 240, and 480 V single-phase and three phase delta. Convertible from three-phase to single-phase (in field) and vice versa (except 208/54 kW). 277 V single-phase also available. Terminal Block - Factory installed. Allows for easy service connection to block. Magnetic Contactors - Heavy duty; UL rated 100000 cycles. |
Other Standard Features |
N/A
|
Testing and Certifications |
N/A
Meets the thermal efficiency and or standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/ISENA 90.1. iCOMM™ Compatible. |