Catalog
Universal™ induced draft commercial gas water heaters are designed for easy installation in applications requiring large quantities of hot water.
Unit of Measure
Specifications
|
Maximum Recovery
|
Maximum Delivery
|
Dimensions
|
Clearances to Combustibles
|
Electrical Characteristics
|
Features and Benefits
|
Warranty
|
General Information
|
Note
Specifications
Manufacturer |
N/A Rheem® |
Maximum Working Pressure |
N/A 160 psi |
Tank Capacity |
N/A 246 L100 U.S. gal |
Input Power |
N/A 360000 BTU/hr |
Thermal Efficiency |
N/A 80 % |
Recovery at 40 ºF Temperature Rise |
N/A 873 U.S. gal/h |
Minimum to Recovery Contents |
N/A 17 |
Top Inlet/Outlet Water Connection |
N/A 1-1/2 in38 mm |
Front Side Water Connection |
N/A 2 in51 mm |
Rear Side Water Connection |
N/A 2 in51 mm |
Standard Approximate Shipping Weight |
N/A 795 lb360 kg |
ASME Approximate Shipping Weight |
N/A 835 lb378 kg |
Side Clearance to Combustibles |
N/A 1 in25 mm |
Rear Clearance to Combustibles |
N/A 1 in25 mm |
Type |
N/A Liquid Propane Gas Natural Gas |
Size |
N/A C |
Style |
N/A Universal™ Induced Draft |
Industry Standards |
N/A AHRI Certified® ANSI Z-21.10.3 - CSA 4.3 ASHRAE Standards ASME Certified CSA® Certified UL® Listed |
Maximum Recovery
Recovery at 22 ºC Temperature Rise |
N/A 3304 L/h |
Recovery at 50 ºF Temperature Rise |
N/A 698 U.S. gal/h |
Recovery at 28 ºC Temperature Rise |
N/A 2643 L/h |
Recovery at 60 ºF Temperature Rise |
N/A 582 U.S. gal/h |
Recovery at 33 ºC Temperature Rise |
N/A 2202 L/h |
Recovery at 70 ºF Temperature Rise |
N/A 499 U.S. gal/h |
Recovery at 39 ºC Temperature Rise |
N/A 1888 L/h |
Recovery at 80 ºF Temperature Rise |
N/A 436 U.S. gal/h |
Recovery at 45 ºC Temperature Rise |
N/A 1652 L/h |
Recovery at 90 ºF Temperature Rise |
N/A 388 U.S. gal/h |
Recovery at 50 ºC Temperature Rise |
N/A 1468 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 349 U.S. gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 1321 L/h |
Recovery at 110 ºF Temperature Rise |
N/A 317 U.S. gal/h |
Recovery at 61 ºC Temperature Rise |
N/A 1201 L/h |
Recovery at 120 ºF Temperature Rise |
N/A 291 U.S. gal/h |
Recovery at 67 ºC Temperature Rise |
N/A 1101 L/h |
Recovery at 130 ºF Temperature Rise |
N/A 269 U.S. gal/h |
Recovery at 72 ºC Temperature Rise |
N/A 1016 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 249 U.S. gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 944 L/h |
Maximum Delivery
Maximum Delivery at 100 ºF (5 Minutes) |
N/A 99 U.S. gal |
Maximum Delivery at 37.7 ºC (5 Minutes) |
N/A 375 L |
Maximum Delivery at 100 ºF (10 Minutes) |
N/A 128 U.S. gal |
Maximum Delivery at 37.7 ºC (10 Minutes) |
N/A 485 L |
Maximum Delivery at 100 ºF (15 Minutes) |
N/A 157 U.S. gal |
Maximum Delivery at 37.7 ºC (15 Minutes) |
N/A 596 L |
Maximum Delivery at 100 ºF (20 Minutes) |
N/A 186 U.S. gal |
Maximum Delivery at 37.7 ºC (20 Minutes) |
N/A 706 L |
Maximum Delivery at 100 ºF (30 Minutes) |
N/A 245 U.S. gal |
Maximum Delivery at 37.7 ºC (30 Minutes) |
N/A 927 L |
Maximum Delivery at 100 ºF (45 Minutes) |
N/A 332 U.S. gal |
Maximum Delivery at 37.7 ºC (45 Minutes) |
N/A 1258 L |
Maximum Delivery at 100 ºF (60 Minutes) |
N/A 419 U.S. gal |
Maximum Delivery at 37.7 ºC (60 Minutes) |
N/A 1588 L |
Maximum Delivery at 100 ºF (120 Minutes) |
N/A 768 U.S. gal |
Maximum Delivery at 37.7 ºC (120 Minutes) |
N/A 2911 L |
Maximum Delivery at 100 ºF (180 Minutes) |
N/A 1117 U.S. gal |
Maximum Delivery at 37.7 ºC (180 Minutes) |
N/A 4234 L |
Dimensions
Features and Benefits
Features and Benefits |
N/A
The tighter the commercial retrofit, the more you will appreciate how the Universal™'s compact size and multiple water connections simplify installations. Choose from 80% thermal efficiency models that range from 250000 to 360000 BTU/hr and have maximum temperature setting of 180 degrees Fahrenheit. Space Saver Design The short height and narrow jacket diameter, plus the top, front and rear water inlets/outlets offer the ultimate in installation flexibility. System Sentinel™ LED Diagnostic System Our exclusive diagnostic system, with glowing LED lights, verifies system operation sequence by sequence. Patented Technology Universal™'s proprietary steel formulation, patented multi-flue design, combined with two coats of porcelain enamel, results in a superior heat exchanger design. Stainless Steel Burners Precision burners, raised port design, are formed from high chromium stainless steel. Each burner assembly slides out like a drawer for quick inspection and maintenance. Factory Installed Draft Inducer Provides an induced draft allowing higher BTU's to be vented through a 6" vent. Full-port, Full-flow Drain Valve Factory installed brass drain valve allows for faster draining and servicing. Direct Spark-to-Pilot Ignition System Energy saving ignition that ignites pilot only when there is a call for heat. Altitude Certifications Up to 5200 feet for natural gas and 2000 feet for LP. Patented Anode Rods Anode design utilizes multiple magnesium rods to ensure corrosion resistance for a long tank life. |
General Information
General Information |
N/A
Efficiency All models tested according to ANSI test procedures, and meet or exceed the thermal efficiency and standby loss requirements of ASHRAE standard (EPact). Also exceeds energy efficiency codes of all states including California Energy Commission (CEC). Safety and Construction Design certified by CSA: For operation at 180 degrees; meets all safety and construction requirement of ANSI Z-21.10.3; as an automatic storage or instantaneous water heater; as an automatic circulating tank water heater; and for operation on combustible floors and in alcove installations. Certified for 150 psi maximum working pressure (160 psi for ASME models). Optional Construction ASME construction is available on designated models. UL Sanitation (NSF5) compliant models are available when equipped with optional seal kit (Part No. AM35450). |