Catalog
Compact commercial electric units have a Fused Ceramic Shield applied under pressure and fired at 1600 ºF to completely cover the tank interior. This provides a tough interior surface for storage tanks and maximum protection against the wearing effects of high-volume and high temperature water.
Unit of Measure
Specifications
Manufacturer |
N/A American® Water Heater Company |
Capacity |
N/A 6 gal |
Standard Voltage |
N/A 120 V |
Standard Input Power |
N/A 1.5 kW |
Maximum Input Power |
N/A 4.5 kW |
Element Power |
N/A 5500 W |
Full Load Current Single Phase 240 V |
N/A 22.9 A |
Full Load Current Single Phase 277 V |
N/A 19.9 A |
Full Load Current Single Phase 480 V |
N/A 11.5 A |
Voltage |
N/A 240 V277 V480 V |
Phase |
N/A Single |
Water Connection |
N/A 3/4 in |
Test Pressure |
N/A 300 psi |
Working Pressure |
N/A 150 psi |
Style |
N/A Utility |
Size |
N/A C |
Type |
N/A Electric |
Industry Standards |
N/A UL® 174 |
Maximum Recovery
Recovery at 40 ºF Temperature Rise |
N/A 56.4 gal/h |
Recovery at 50 ºF Temperature Rise |
N/A 45.1 gal/h |
Recovery at 60 ºF Temperature Rise |
N/A 37.5 gal/h |
Recovery at 70 ºF Temperature Rise |
N/A 32.2 gal/h |
Recovery at 80 ºF Temperature Rise |
N/A 28.2 gal/h |
Recovery at 90 ºF Temperature Rise |
N/A 25.4 gal/h |
Recovery at 100 ºF Temperature Rise |
N/A 22.5 gal/h |
Features
Features |
N/A
|