Catalog
Unit of Measure
Specifications
|
Dimensions
|
Maximum Recovery
|
Electrical Characteristics
|
Clearances to Combustibles
|
Water Connection
|
Features
|
Testing and Certifications
|
Other Features
|
Warranty
|
Note
Specifications
Manufacturer |
N/A American® Water Heater Company |
Input Power |
N/A 310000 KBTU/hr91 kW |
Capacity |
N/A 85 U.S. gal322 L |
Thermal Efficiency |
N/A 82 % |
Standard Type |
N/A Non-ASME |
Minimum Gas Supply Pressure |
N/A 0.87 kPa3.50 inWc |
Maximum Gas Supply Pressure |
N/A 14 inWc3.48 kPa |
Standard Approximate Shipping Weight |
N/A 850 lb386 kg |
Options |
N/A
|
Type |
N/A Natural Gas |
Style |
N/A Ultra-Low NOx Heavy-Duty |
Size |
N/A C |
Industry Standards |
N/A AHRI Certified® ASHRAE/IESNA 90.1 ASME Certified CSA® Certified UL® Listed |
Dimensions
Maximum Recovery
Recovery at 36 ºF Temperature Rise |
N/A 849 gal/h |
Recovery at 20 ºC Temperature Rise |
N/A 3216 L/h |
Recovery at 40 ºF Temperature Rise |
N/A 765 gal/h |
Recovery at 22 ºC Temperature Rise |
N/A 2894 L/h |
Recovery at 50 ºF Temperature Rise |
N/A 612 gal/h |
Recovery at 28 ºC Temperature Rise |
N/A 2315 L/h |
Recovery at 54 ºF Temperature Rise |
N/A 566 gal/h |
Recovery at 30 ºC Temperature Rise |
N/A 2144 L/h |
Recovery at 60 ºF Temperature Rise |
N/A 510 gal/h |
Recovery at 33 ºC Temperature Rise |
N/A 1929 L/h |
Recovery at 70 ºF Temperature Rise |
N/A 437 gal/h |
Recovery at 39 ºC Temperature Rise |
N/A 1654 L/h |
Recovery at 72 ºF Temperature Rise |
N/A 425 gal/h |
Recovery at 40 ºC Temperature Rise |
N/A 1608 L/h |
Recovery at 80 ºF Temperature Rise |
N/A 382 gal/h |
Recovery at 44 ºC Temperature Rise |
N/A 1447 L/h |
Recovery at 90 ºF Temperature Rise |
N/A 340 gal/h |
Recovery at 50 ºC Temperature Rise |
N/A 1286 L/h |
Recovery at 100 ºF Temperature Rise |
N/A 306 gal/h |
Recovery at 56 ºC Temperature Rise |
N/A 1158 L/h |
Recovery at 108 ºF Temperature Rise |
N/A 283 gal/h |
Recovery at 60 ºC Temperature Rise |
N/A 1072 L/h |
Recovery at 110 ºF Temperature Rise |
N/A 278 gal/h |
Recovery at 61 ºC Temperature Rise |
N/A 1052 L/h |
Recovery at 120 ºF Temperature Rise |
N/A 255 gal/h |
Recovery at 67 ºC Temperature Rise |
N/A 965 L/h |
Recovery at 126 ºF Temperature Rise |
N/A 243 gal/h |
Recovery at 70 ºC Temperature Rise |
N/A 919 L/h |
Recovery at 130 ºF Temperature Rise |
N/A 235 gal/h |
Recovery at 72 ºC Temperature Rise |
N/A 890 L/h |
Recovery at 140 ºF Temperature Rise |
N/A 218 gal/h |
Recovery at 78 ºC Temperature Rise |
N/A 827 L/h |
Clearances to Combustibles
Sides and Rear Clearance to Combustibles |
N/A 0 in |
Top Cover Clearance to Combustibles |
N/A 12 in |
Sides and Rear Clearance to Non-Combustibles |
N/A 0 in |
Top Cover Clearance to Non-Combustibles |
N/A 12 in |
Water Connection
Top Inlet Water Connection |
N/A 1-1/2 in |
Front Inlet Water Connection |
N/A 1-1/2 in |
Back Inlet Water Connection |
N/A 1-1/2 in |
Top Outlet Water Connection |
N/A 1-1/2 in |
Front Outlet Water Connection |
N/A 1-1/2 in |
Back Outlet Water Connection |
N/A 1-1/2 in |
Features
Features |
N/A
82% thermal efficiency means lower operating costs. Fan Assisted Combustion
|
Testing and Certifications
Testing and Certifications |
N/A
Approval Ratings and Certification
|
Other Features
Other Features |
N/A
|