Catalog
Designed for use as a recovery heater having its own storage tank or booster for supplying sanitizing rinse water for dishwashing.
Unit of Measure

Specifications

Manufacturer

A. O. Smith®

Input Power

9 kW30717 BTU/hr

Number of Elements

3

Element Power

3000 W

Tank Capacity

50 gal189 L

Equipment Grade

Commercial

Inlet/Outlet (NPT)

1-1/4 in3.2 cm

Approximate Shipping Weight

265 lb120 kg

Industry Standards

ASHRAE/IESNA 90.1 ASME Certified

Electrical Characteristics

Full Load Current Single Phase 208 V

43.3 A

Full Load Current Single Phase 240 V

37.5 A

Full Load Current Single Phase 277 V

32.5 A

Full Load Current Single Phase 480 V

18.8 A

Full Load Current Three Phase 208 V

25.0 A

Full Load Current Three Phase 240 V

21.7 A

Full Load Current Three Phase 480 V

10.8 A

Standard Voltage

208 V240 V480 V

Dimensions

Schematic


Schematic Drawing for Gold Xi™ DVE Series Commercial Electric Water Heaters

Dimension A

55-3/4 in142 cm

Dimension B

21-3/4 in55.2 cm

Dimension C

27 in68.6 cm

Maximum Recovery (ºF)

Recovery at 30 ºF Temperature Rise

123 gal/h

Recovery at 40 ºF Temperature Rise

92 gal/h

Recovery at 50 ºF Temperature Rise

74 gal/h

Recovery at 60 ºF Temperature Rise

62 gal/h

Recovery at 70 ºF Temperature Rise

53 gal/h

Recovery at 80 ºF Temperature Rise

46 gal/h

Recovery at 90 ºF Temperature Rise

41 gal/h

Recovery at 100 ºF Temperature Rise

37 gal/h

Recovery at 110 ºF Temperature Rise

34 gal/h

Recovery at 120 ºF Temperature Rise

31 gal/h

Recovery at 130 ºF Temperature Rise

28 gal/h

Recovery at 140 ºF Temperature Rise

26 gal/h

Maximum Recovery (ºC)

Recovery at 17 ºC Temperature Rise

465 L/h

Recovery at 22 ºC Temperature Rise

349 L/h

Recovery at 28 ºC Temperature Rise

279 L/h

Recovery at 33 ºC Temperature Rise

233 L/h

Recovery at 39 ºC Temperature Rise

199 L/h

Recovery at 45 ºC Temperature Rise

174 L/h

Recovery at 50 ºC Temperature Rise

155 L/h

Recovery at 56 ºC Temperature Rise

140 L/h

Recovery at 61 ºC Temperature Rise

127 L/h

Recovery at 67 ºC Temperature Rise

116 L/h

Recovery at 72 ºC Temperature Rise

107 L/h

Recovery at 78 ºC Temperature Rise

100 L/h

Features

Features

Economy Mode Operation - Control system automatically lowers the Operating Set Point by a programmed value during user-defined time periods. Helps reduce operating costs during unoccupied or off-peak demand periods.

Linear Sequencing - Banks of heating elements (3 elements per bank) are energized according to adjustable (1 to 20º) differential set points for each bank. First bank on is the last bank off. Helps reduce current surge and provides accurate water temperature control.

Goldenrod Elements - All DVE models ship standard with patented Goldenrod 24K gold plated elements. Goldenrod elements provide long life with superior scaling resistance.

Glass-Lined Tank - Three sizes; 50, 80, and 119 gallon capacity. Tank interior is coated with glass specially developed by A. O. Smith® for water heater use. Tanks rated at 150 psi working pressure; tested at 300 psi. Foam insulation reduces costly heat loss. ASME (optional) maximum working pressure is 150 psi.

Power Circuit Fusing - Protects elements and contactors from short circuits, overloading or line surges. Meets National Electric Code requirements (fusing required when current draw exceeds 48 amps).

Standard Voltages - 208, 240, and 480 V single-phase and three phase delta. Convertible from three-phase to single-phase (in field) and vice versa (except 208/54 kW). 277 V single-phase also available.

Terminal Block - Factory installed. Allows for easy service connection to block.

Magnetic Contactors - Heavy duty; UL rated 100000 cycles.

Other Standard Features

Other Standard Features

  • Immersion style thermostats
  • Simplified circuitry, color coded for ease of service
  • Hinged control compartment door for quick, easy access
  • Two anode rods for maximum corrosion protection
  • Cabinet has bonderized undercoat with baked enamel finish
  • Top outlet, side inlet and relief valve openings
  • Nipple and brass drain valve
  • CSA® certified and ASME rated T&P relief valve

Testing and Certifications

Testing and Certifications

Meets the thermal efficiency and or standby loss requirements of the U.S. Department of Energy and current edition of ASHRAE/ISENA 90.1.

iCOMM™ Compatible.

Options

Options

Manifold Kits with Isolation Valves - Available for multiple installations. Two heaters #9003429205. Three heaters #9003430205. Four heaters #9003431205.

International Voltages - 220, 380, 400, 415, 480, 575, and 600 volts three-phase available with Y connected elements.

Warranty

Warranty

  • 3-Year Limited Tank Warranty.

Note

Note

For Full Load Current Single Phase 277 V:
Elements available in incoloy only.